Bat charger: Debounce recharge from trickle state

Reduce the recharge voltage threshold and consider it for transition
between trickle and bulk charging such that the trickle state is
maintained longer and batteries don't get recharged multiple times
per day.

This is also necessary for nanogrid interface control, which can try to
maintain a voltage between recharge and trickle voltage by exporting
excess solar energy towards the grid. If the battery voltage is maintained
at the trickle voltage, the solar input power might be reduced and not all
available power can be used.
This commit is contained in:
Martin Jäger
2021-06-01 18:02:52 +02:00
parent a4760ebcb8
commit 8de5c595c2
+4 -2
View File
@@ -53,7 +53,7 @@ void battery_conf_init(BatConf *bat, int type, int num_cells, float nominal_capa
case BAT_TYPE_GEL:
bat->voltage_absolute_max = static_cast<float>(num_cells) * 2.45F;
bat->topping_voltage = static_cast<float>(num_cells) * 2.4F;
bat->voltage_recharge = static_cast<float>(num_cells) * 2.3F;
bat->voltage_recharge = static_cast<float>(num_cells) * 2.2F;
// Cell-level thresholds based on EN 62509:2011 (both thresholds current-compensated)
bat->voltage_load_disconnect = static_cast<float>(num_cells) * 1.95F;
@@ -550,7 +550,9 @@ void Charger::charge_control(BatConf *bat_conf)
time_target_voltage_reached = uptime();
}
if (uptime() - time_target_voltage_reached > bat_conf->trickle_recharge_time)
if ((uptime() - time_target_voltage_reached > bat_conf->trickle_recharge_time) &&
port->bus->voltage_filtered < port->bus->sink_control_voltage(
bat_conf->voltage_recharge))
{
// the battery was discharged: trickle voltage could not be reached anymore
port->pos_current_limit = bat_conf->charge_current_max;