Load voltage thresholds adjusted and inhibit added
During tests, the deep discharge counter increased by several 100 counts per day under certain circumstances, most probably because of quite small battery making the voltage toggle between disconnect and reconnect voltage. This commit suggests several improvements. - Load reconnect voltage increased - Don't reconnect before waiting at least 1h (lvd_timestamp in load.cpp) - SOC filter calculation slightly changed to make sure 100% is reached fast enough.
This commit is contained in:
+4
-1
@@ -238,6 +238,8 @@ void usb_state_machine(load_output_t *load)
|
||||
}
|
||||
}
|
||||
|
||||
static time_t lvd_timestamp = 0; // stores when the load was disconnected last time
|
||||
|
||||
void load_state_machine(load_output_t *load, bool source_enabled)
|
||||
{
|
||||
//printf("Load State: %d\n", load->switch_state);
|
||||
@@ -254,12 +256,13 @@ void load_state_machine(load_output_t *load, bool source_enabled)
|
||||
load->switch_state = LOAD_STATE_DISABLED;
|
||||
}
|
||||
else if (source_enabled == false) {
|
||||
lvd_timestamp = time(NULL);
|
||||
load_switch_set(false);
|
||||
load->switch_state = LOAD_STATE_OFF_LOW_SOC;
|
||||
}
|
||||
break;
|
||||
case LOAD_STATE_OFF_LOW_SOC:
|
||||
if (source_enabled == true) {
|
||||
if (source_enabled == true && time(NULL) - lvd_timestamp > 60*60) { // wait at least one hour
|
||||
if (load->enabled_target == true) {
|
||||
load_switch_set(true);
|
||||
load->switch_state = LOAD_STATE_ON;
|
||||
|
||||